Skip to main content

PACKAGED CHP SYSTEM HIGHLIGHTS

CHP Packager Avco Supply Inc
Model XRGI 25
Thermal Outputs Hot Water
Assurance Plan Depends on location
Grid Connection Type Grid Parallel Only
Outdoor Placement Indoor Only

KEY PERFORMANCE DATA

CHP Design Efficiency 1 82.9%
Prime Mover Reciprocating engines
EC POWER
XRGI 25
Number of Prime Movers 1
Net Power Output (kW)2 24
  1. (Net Power Output + Thermal Output) / Energy Input at 59°F and 100% gross power
  2. Net Power Output is Gross Prime Mover Power less CHP system parasitics, less fuel gas booster if required and less chiller parasitics during chiller operation
  3. Hot water capacity is usable energy assuming 180F supply and minimum allowable return temperature to the Packaged CHP System

Avco Supply Inc | Packager Description

Distributor of Lochinvar EC Power Micro Cogen systems.
Help with design & local rebates.

Lochinvar, LLC | OEM Packager Description

Lochinvar, LLC is the leading manufacturer of high-efficiency, boilers, water heaters, pool heaters packaged water heating systems and storage tanks. Additionally, in partnership with EC POWER, Lochinvar now offers innovative cogeneration water heating solutions. Based in Lebanon, Tenn., with facilities in Chicago, Detroit, Orlando, Phoenix, Pompano Beach and Dallas. For more information about Lochinvar, visit www.Lochinvar.com. For more information about EC POWER, visit www.ecpower.eu

Certifications

Lochinvar, LLC has submitted certification that this Packaged CHP System is built in accordance with the following manufacturing and/or design:

  • IEEE 1547 Compliance for protective relay and 52G breaker
  • UL1741
  • LU2200

Installation Experience

-

Total Company Installs

Total CHP systems installed by Avco Supply Inc

-

Total Company Installs in PA

Total CHP systems installed by Avco Supply Inc in PA

2

Installs of this Package

Total number of this model Packaged CHP system installed

-

Company Installs of this Package

Installs of this model by Avco Supply Inc

Note: Installations of Packaged CHP Systems may include systems outside the USA, and some may be 50 hertz applications.
  100% Gross Power 75% Gross Power 50% Gross Power
Ambient Temperature 95°F 59°F 0°F 95°F 59°F 0°F 95°F 59°F 0°F
CHP Fuel Input (MMBtu per hour HHV) 0.29 0.29 0.29 0.22 0.22 0.22 0.18 0.18 0.18
Power
Gross Electricity Output (kW) 24 24 24 18 18 18 12 12 12
Net Electricity Output (kW) 24 24 24 18 18 18 12 12 12
Net Electric Efficiency % (HHV) 27.8 27.8 27.8 27.3 27.3 27.3 22.0 22.0 22.0
Hot Water
Supply Temp to Site (°F) 180 °F 180 °F 180 °F
HW flow (GPM) 16 16 16 16 16 16 16 16 16
Return Temp from Site (°F) 160 160 160 164 164 164 166 166 166
Hot Water Capacity (MMBtu/hr) 0.16 0.16 0.16 0.13 0.13 0.13 0.11 0.11 0.11
Thermal Efficiency % (HHV) 55.2 55.2 55.2 59.1 59.1 59.1 61.1 61.1 61.1
CHP Fuel Use Eff % (Hot Water Operation) 82.9 82.9 82.9 86.4 86.4 86.4 83.1 83.1 83.1
*Be sure that the site thermal load will handle return water temperatures to the CHP system as stated. (e.g. 5 to 10 F below) Otherwise, hot water capacity will be less than stated. Contact the Packager/Solution Provider for details.
Emissions
Emissions Aftertreatment Stoichiometric engine with 3-way catalyst
NOx Emissions without Aftertreatment (lb/MWhe) 0.04
CO Emissions without Aftertreatment (lb/MWhe) 0.04
Fuel Gas
Fuel Gas Pressure to Packaged CHP System (psig) 1 25 50 100 300
Fuel Gas Booster Compressor Power Required (kW) n/a n/a n/a n/a n/a
  Manufacturer Model Type Capacity
Generator EC POWER XRGI 25 Induction 25 kW
Grid Interconnection Grid Parallel Only
  Manufacturer Type
Hot Water Heat Recovery EC POWER Q70
System Sound @ 1m height and 10m distance (dBA) 49.0 dBA
  Width in Feet Length in Feet Height in Feet Weight in Pounds
System / Component
Prime Mover/Generator system (Includes maintenance clearances) 2.5 3.7 3.9 1,500
Total System Layout (Includes maintenance clearances) 8.0 8.0 7.3 1,500
Largest part for delivery 2.6 4.6 6.7 1,685
Heaviest part for delivery 2.6 4.6 6.7 1,685